Air Pressure Differences over External Walls in New and Retrofitted Schools and Daycare Centers

Kauppinen, Antti; Kiviste, Mihkel; Pirhonen, Joni; Tuominen, Eero; Laukkarinen, Anssi; Huttunen, Petteri; Vinha, Juha (2022-10)

 
Avaa tiedosto
buildings_12_01629_v2.pdf (3.434Mt)
Lataukset: 



Kauppinen, Antti
Kiviste, Mihkel
Pirhonen, Joni
Tuominen, Eero
Laukkarinen, Anssi
Huttunen, Petteri
Vinha, Juha
10 / 2022

Buildings
1629
doi:10.3390/buildings12101629
Näytä kaikki kuvailutiedot
Julkaisun pysyvä osoite on
https://urn.fi/URN:NBN:fi:tuni-202211228536

Kuvaus

Peer reviewed
Tiivistelmä
<p>Air pressure differences are a key factor in the behavior of building ventilation and air leakages through the building envelope. Field measurements of the air pressure differences over the building envelope were conducted in 24 Finnish municipal service buildings. The measured buildings were mainly schools and daycare centers, of which half were new buildings and half recently retrofitted. All buildings had mechanical ventilation. The measurements were conducted during 2016–2018. The total number of measurement points was 100, and the duration of individual time series varied. According to the results, the mean air pressure difference was within the range of national recommendations (small underpressure indoors) in 81–89% of measurement points, but some cases experienced either strong underpressure or overpressure conditions. In some cases, the air pressure difference showed a clear stepwise constant behavior, while other cases showed larger temporal variation. The conditions varied between different operating situations and the time of year. The study also supports the current recommendation that air pressure difference measurements should be done as continuous measurements of at least one week duration.</p>
Kokoelmat
  • TUNICRIS-julkaisut [23485]
Kalevantie 5
PL 617
33014 Tampereen yliopisto
oa[@]tuni.fi | Tietosuoja | Saavutettavuusseloste
 

 

Selaa kokoelmaa

TekijätNimekkeetTiedekunta (2019 -)Tiedekunta (- 2018)Tutkinto-ohjelmat ja opintosuunnatAvainsanatJulkaisuajatKokoelmat

Omat tiedot

Kirjaudu sisäänRekisteröidy
Kalevantie 5
PL 617
33014 Tampereen yliopisto
oa[@]tuni.fi | Tietosuoja | Saavutettavuusseloste