Parametric CFD study for finding the optimal tube arrangement of a fin-and-tube heat exchanger with plain fins in a marine environment

Välikangas, Turo; Folkersma, Mikko; Dal Maso, Miikka; Keskitalo, Tuomo; Peltonen, Petteri; Vuorinen, Ville (2021-10-22)

 
Avaa tiedosto
Parametric_CFD_study_for_finding.pdf (2.794Mt)
Lataukset: 



Välikangas, Turo
Folkersma, Mikko
Dal Maso, Miikka
Keskitalo, Tuomo
Peltonen, Petteri
Vuorinen, Ville
22.10.2021

Applied Thermal Engineering
117642
doi:10.1016/j.applthermaleng.2021.117642
Näytä kaikki kuvailutiedot
Julkaisun pysyvä osoite on
https://urn.fi/URN:NBN:fi:tuni-202111128364

Kuvaus

Peer reviewed
Tiivistelmä
<p>In the past, fin-and tube heat exchanger (FTHE) tube pattern ratios have been largely based on ad-hoc design principles. Here, we investigate the optimal tube arrangements for a FTHE with plain fins in marine environments represented by two different air types; one for unfiltered air with high condensation rate and one for clean dry filtered air conditions. The thermal-hydraulic efficiency of the FTHE design is measured by comparing a modified ratio of Colburn j-factor and Fanning friction factor. The regression model generated from the CFD data is then used to identify the maximum efficiency for two design specific fin pitches separately. We identified two optimal tube patterns: one for a large fin pitch for unfiltered air, and another for a small fin pitch for filtered air. Manufacturing restrictions were found to significantly limit the maximum achievable efficiency of a tube pattern. By neglecting the related manufacturing restrictions, 4% higher efficiency for a fin pitch of 1.5 mm and 23% higher efficiency for a fin pitch of 3.5 mm is achieved. Without any application specific limitations or manufacturing restrictions the fin pitch 1.5 mm can have a 36% increased efficiency than fin pitch 3.5 mm. These novel results show that development in manufacturing have potential for significant improvements in thermal-hydraulic efficiency.</p>
Kokoelmat
  • TUNICRIS-julkaisut [20173]
Kalevantie 5
PL 617
33014 Tampereen yliopisto
oa[@]tuni.fi | Tietosuoja | Saavutettavuusseloste
 

 

Selaa kokoelmaa

TekijätNimekkeetTiedekunta (2019 -)Tiedekunta (- 2018)Tutkinto-ohjelmat ja opintosuunnatAvainsanatJulkaisuajatKokoelmat

Omat tiedot

Kirjaudu sisäänRekisteröidy
Kalevantie 5
PL 617
33014 Tampereen yliopisto
oa[@]tuni.fi | Tietosuoja | Saavutettavuusseloste