Cost-optimal energy performance measures in a new daycare building in cold climate
Sankelo, Paula; Jokisalo, Juha; Nyman, Jonathan; Vinha, Juha; Sirén, Kai (2018-03-15)
Sankelo, Paula
Jokisalo, Juha
Nyman, Jonathan
Vinha, Juha
Sirén, Kai
15.03.2018
International Journal of Sustainable Energy
This publication is copyrighted. You may download, display and print it for Your own personal use. Commercial use is prohibited.
Julkaisun pysyvä osoite on
https://urn.fi/URN:NBN:fi:tuni-201911186054
https://urn.fi/URN:NBN:fi:tuni-201911186054
Kuvaus
Peer reviewed
Tiivistelmä
<p>New municipal service buildings must be energy effective, and cost-optimality is one of the criteria for selecting the suitable energy performance improvement measures. A daycare building in a cold climate was studied by means of simulation-based, multi-objective optimisation. Using a genetic algorithm, both target energy use and life-cycle cost of the selected measures were minimised. It was found that extensive insulation of the building envelope is not a cost-optimal method to reduce the daycare building energy use. Improving energy efficiency of the ventilation system, utilising solar energy on-site and employing a light control strategy are preferable ways of improving the building energy performance. Ground-source heat pump is a more cost-optimal heating system for the daycare building than district heating. The cost-optimal sizing of the heat pump is small, only 28% of the required maximum heating power. Abbreviations: AHU: air handling unit; CAV: constant air volume; COMBI: comprehensive development of nearly zero-energy municipal service buildings; COP: coefficient of performance; DH: district heating; DHW: domestic hot water; EPBD: energy performance of buildings directive; EU: European Union; FINVAC: Finnish Association of HVAC Societies; GSHP: ground-source heat pump; HRU: heat recovery unit; IDA ICE: IDA Indoor Climate and Energy; LED: light-emitting diode; MOBO: multi-objective building optimisation tool; NSGA-II: Non-dominated Sorting Genetic Algorithm II; nZEB: nearly zero-energy building; PV: photovoltaic; TRY: test reference year; VAV: variable air volume; ZEB: zero-energy building</p>
Kokoelmat
- TUNICRIS-julkaisut [24353]