Indirect NO<sub>x</sub> emission monitoring in natural gas fired boilers
Korpela, Timo; Kumpulainen, Pekka; Majanne, Yrjö; Häyrinen, Anna; Lautala, Pentti (2017-08-01)
Lataukset:
Korpela, Timo
Kumpulainen, Pekka
Majanne, Yrjö
Häyrinen, Anna
Lautala, Pentti
01.08.2017
Control Engineering Practice
This publication is copyrighted. You may download, display and print it for Your own personal use. Commercial use is prohibited.
Julkaisun pysyvä osoite on
https://urn.fi/URN:NBN:fi:tty-201708021643
https://urn.fi/URN:NBN:fi:tty-201708021643
Kuvaus
Peer reviewed
Tiivistelmä
<p>New emission regulations will increase the need for inexpensive NO<sub>x</sub> emission monitoring solutions also in smaller power plants. The objective in this study is to find easily maintainable and transparent but still valid models to predict NO<sub>x</sub> emissions in natural gas fired hot water boilers utilizing existing process instrumentation. With a focus on long-term applicability in practical installations, the performance of linear regression is compared in two municipal 43 MW boilers with three widely used nonlinear methods: multilayer perceptron, support vector regression, and fuzzy inference system. The linear models were the most applicable providing the best estimation results (relative error of 1 applications in practise. However, each boiler model should be identified individually.</p>